B-1.1, r. 2 - Construction Code

Full text
8.145. A dispenser installed or altered in a motor fuel dispensing outlet must comply with the clearances in the following Table 5:
TABLE 5
MOTOR FUEL DISPENSER CLEARANCES (M)



Dispenser Unattended Marina User outlet Airport outlet
outlet self-serve outlet

facility


From a building, 4.5(1) 6(1) 5 1(3) 15
except a booth


From property 4.5(1) 6(1) 4.5(1) 4.5(3) 15
lines


From a stationary 6(2) 6(2) 8 7.5(3) 6(2)
ignition source


From a building __ __ __ 4.5(3) __
opening other
than a booth
opening


From a dock,
wharf, pier or __ __ 5 __ 5
pontoon or
approach thereto

(1) If a petroleum product installation is altered, a dispenser installed before 1973 need not be relocated or may be replaced by another dispenser at the same place if it has the same number of dispensing hoses and dispenses the same number of products. In the case of a marina outlet, the shore is not to be considered a property line.
(2) Applies only to a fuel dispenser dispensing a Class 1 petroleum product.
(3) If a petroleum product installation is altered, a dispenser installed before 11 July 1991 need not be relocated or may be replaced by another dispenser at the same place if it has the same number of dispensing hoses and dispenses the same number of products.
In addition, the clearances must be increased, if necessary, so that any vehicle to be fuelled from that dispenser is completely within the property lines of the place where the dispenser is located.
O.C. 220-2007, s. 1.